Model : SJ00-1KVA
ups-1kva
ups-1kva
TECHNICAL SPECIFICATION
FEATURES
DOWNLOAD
UPS system model SJ00-1KVA
Phase Single phase with ground
Capacity 1KVA/800W
Input
Nominal voltage100/110/115/120/127VAC or 200/208/220/230/240vac
Input voltage range 55-145 VAC or 110-300 VAC
Frequency range 40HZ~70HZ
Power factor ≥ 0.99 @ Nominal Voltage(100% load)
Output
Output voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
Voltage regulation ± 1%
Frequency range (Synchronized Range) 47 ~ 53 HZ or57 ~ 63 HZ
Frequencyrange (Batt. Mode) 50 HZ or 60 HZ ± 0.1 HZ
Current crest ratio 3:1
Harmonic distortion ≤ 3 % THD (Linear Load),≤ 6 % THD (Non-Linear Load)
Transform time :
AC to DCZero
Inverter to Bypass 4 ms (Typical)
Waveform (Batt. Mode) Pure sinewave
Efficiency
To AC mode88%
To Battery mode 88%
Battery
Standard model machine :
Battery type12V9AH
Quantity 2
Standard charging time4 hours charge to 90%
The maximum charge current 1A
Charging voltage27.3VDC±1%
Long-Run model :
Battery typeDepending on the capacity of external batteries
Numbers 3
Charging current (max.) 1.0A/2.0A/4.0A/6.0 A
Charging voltage41.0VDC ± 1%
Indicators
LCD Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault
Alarm
Battery modeSounding every 4 seconds
Low battery Sounding every seconds
Overload Sounding twice every second
Fault Continously sounding
Physical
Standard model :
Dimension(D*W*H)mm 397*145*220
Net weight(kgs)9.3
Long-Run model :
Dimension(D*W*H)mm 282 x 145 x 220
Net weight(kgs)4.1
Environment
Humidity20-90 % RH @ 0- 40°C (non-condensing)
Noise level Less than 50dBA @ 1 Meter
Management
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
  • True double-conversiony.
  • Microprocessor control optimizes reliability.
  • Input power factor correction.
  • Output power factor 0.8.
  • Wide input voltage(110 V - 300 V).
  • Converter mode available.
  • ECO mode for energy saving.
  • Generator compatible.
  • Charger capacity expansion to 6A for long-run models.
  • Smart SNMP works well with either USB or RS-232 together.
  • Comprehensive display allows easy monitoring and access.